Table 530:I103USRCMD Output signalsName Type DescriptionOUTPUT1 BOOLEAN Command output 1OUTPUT2 BOOLEAN Command output 2OUTPUT3 BOOLEAN Command output 3OUTPUT4 BOOLEAN Command output 4OUTPUT5 BOOLEAN Command output 5OUTPUT6 BOOLEAN Command output 6OUTPUT7 BOOLEAN Command output 7OUTPUT8 BOOLEAN Command output 818.7.12.5 SettingsTable 531:I103USRCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)PulseMode SteadyPulsed- - Pulsed Pulse modePulseLength 0.200 - 60.000 s 0.001 0.400 Pulse lengthInfNo_1 1 - 255 - 1 1 Information number for output 1 (1-255)InfNo_2 1 - 255 - 1 2 Information number for output 2 (1-255)InfNo_3 1 - 255 - 1 3 Information number for output 3 (1-255)InfNo_4 1 - 255 - 1 4 Information number for output 4 (1-255)InfNo_5 1 - 255 - 1 5 Information number for output 5 (1-255)InfNo_6 1 - 255 - 1 6 Information number for output 6 (1-255)InfNo_7 1 - 255 - 1 7 Information number for output 7 (1-255)InfNo_8 1 - 255 - 1 8 Information number for output 8 (1-255)18.7.13 Function commands generic for IEC 60870-5-103I103GENCMD18.7.13.1 FunctionalityI103GENCMD is used for transmitting generic commands over IEC 60870-5-103. Thefunction has two outputs signals CMD_OFF and CMD_ON that can be used to implementdouble-point command schemes.Section 18 1MRK 511 365-UUS AStation communication658 Phasor measurement unit RES670 2.1 ANSITechnical manual