V6.230 20131017136Enter:87/1This will add Load to the log. Type 0 to remove from the log.12.5 Viewing the Data LogThe data log can be viewed on a PC through the RS-232 interface. Downloadingthe data log does not erase the log. The data log is received as a commadelimited ASCII data. It can be captured for use in other programs as shown inthe next section.To view the log via a PC, open the terminal emulation program with the settingsused to access the main TTC-1000 menu.First press the Enter key to display the Main Menu:Advanced Power Technologies, LLC; (C) 2004-2008Transformer Temperature Controller V6.23Select:1. VIEW SETPOINT AND LOGIC SETTINGS2. PROGRAM SETPOINT AND LOGIC SETTINGS (2/XXXX)3. VIEW CONFIGURATION SETTINGS4. PROGRAM CONFIGURATION SETTINGS (4/XXXX)5. STATUS6. SEND SETTINGS TO COMPUTER7. SEND SETTINGS TO UNIT (7/XXXX)8. SEND CSV SETTINGS TO UNIT (8/XXXX)9. DOWNLOAD DATA LOG10. DOWNLOAD SOFTWARE PATCH (10/XXXX)11. DIGITAL INPUTS AND TAP POSITION MONITORING12. LOG OFFEnter Code:Enter menu option 9 and press Enter, the data log will be sent to the PC.If no data is logged the data reported through the terminal emulation program willshow:NO DATAEND OF REPORT. STOP TEXT CAPTURE & PRESS 'Enter'Should the log contain data, the terminal emulation program will show:DATE,TIME,TOP OIL,WINDING,LOAD07/31/03,08:46:03,49 ,49 ,93007/31/03,08:36:03,49 ,49 ,93107/31/03,08:26:03,49 ,49 ,93207/31/03,08:16:03,49 ,49 ,93407/31/03,08:06:03,49 ,49 ,93707/31/03,07:56:03,49 ,49 ,940END OF REPORT. STOP TEXT CAPTURE & PRESS 'Enter'