V6.230 2013101780Press YES when you have made the correct selection.For programming from a PC just type the setting for the winding circuit alarmenable on the “Enter:” line as follows:Enter:090/1This will disable the winding circuit probe alarm. Type 0 to enable the alarm.This alarm is for reporting only and does not supervise any of the controlfunctions. If this setting is disabled (DSABL) and a winding circuit alarm occurs,the alarm will still be displayed on the front panel display of the unit. However, itwill not light the front panel alarm LED, nor will it operate the dedicated alarmcontact output.4.14 Setting Date and TimeThe TTC-1000 utilizes a real time clock to maintain date and time. This devicehas two functions. It supplies precise 32 millisecond time ticks for the Real TimeInterrupt and it keeps track of the time, date and day of the week. Also, the time,date, and day are maintained even while the unit is unpowered for 5 days at85ºC. The TTC-1000 powers the RTC through the use of large value capacitorthat eliminates the need for battery backup and is designed to operate over theentire temperature range.Time and date are used to evaluate the TIME set points and data logging.4.14.1 Setting Time and Date Via the Front PanelSetting from the front panel, enter the Configuration menu and press the orarrow button until the setting 088 is displayed:Press the YES button. The 10’s hour digit will flash. Use the or arrow buttonsto set this digit. Use the button to move to the 1’s hour digit and observe thatit flashes. Again use the or arrow buttons to set this digit. Scroll to the 10’sminute digit by pressing the button and observe that it flashes. Use the orarrow buttons to set this digit. Scroll to the 1’s minute digit and observe that itPRGM SETTING 088TIME=00:05PRGM SETTING 090WNDCKTALRM=DSABL