Installation and operating instructions30DAIKIN EKHHP(3/5)00AA2V3DAIKIN Hot water heat pump008.1423444_05 – 08/20167 x Operation, Parameters7.5.3 Parameter factory settingsCode 1Code 2Parameter name Standard factory settingsValue Range Increment Unit0 00 Hot water set temperature for the operating mode "High Output" 55 40 - 60 1 °C01 Hot water set temperature for thermal disinfection 65 50 - 75 1 °C02 Heat retention function switch-on temperature 40 35 - 55 1 °C03 Heat retention switch-off temperature 45 35 - 55 1 °C04 Actvation / deactivation of heat retention function 0 0 - 1 1 —2 00 Start day thermal disinfection (Legionella protection) FR every day — —01 Automatic thermal disinfection with hot water heat pump switched on 0 0 - 1 0 —02 Start time thermal disinfection 23:00 0:00 - 23:00 1:00 h03 Automatic thermal disinfection in "Stand-by" mode 0 0 - 1 1 —04 Holding time thermal disinfection temperature [0-01] 10 5 - 60 1 Min.3 00 Automatic restart after a power failure 1 0 - 1 1 —01 Access authorisation 3 2, 3 1 —02 Hot water set temperature >60 °C 0 0 - 1 1 —4 03 Simultaneous operation of the electrical Booster Heater (BSH) andheat pump0 0 - 3 1 —6 00 Switchng hysteresis of heat pump 14 2 - 20 1 K01 Heat pump switch-off temperature difference 0 0 - 15 1 K02 ECO-Timer (BSH) 120 5 - 120 1 Min.03 Priority of operating mode "High Output" 1 0 - 1 1 —04 Steps in the operating mode "Low Noise" 1 1 - 3 1 —7 00 Behaviour in high/low tariff (HT/NT) - / Smart Grid (SG) mode 0 0 - 3 1 —01 Switching hysteresis Booster-Heater (BSH) when hot water set tem-perature is above the maximum possible hot water temperature inexclusively heat pump mode.2 2 - 20 1 °C02 Setting Emergency mode (use of BSH permitted or not) 0 0 - 1 1 —04 Lower external temperature limit for heat pump operation -15 -25 - 10 1 °CC 00 Not used 0 — — —E Display unit information00 Software version Information value, cannot be changed.01 EEPROM version Information value, cannot be changed.02 Model ID Information value, cannot be changed.These parameters are only accessible in the "Advanced Mode" (see Section 7.5.1).Tab. 7-5 Overview parameter settings