FC 300 Design GuideHow to ProgramParameter Designation Setting0-01 Language1-20 Motor Power [kW]1-22 Motor Voltage [V]1-23 Motor Frequency [Hz]1-24 Motor Current [A]1-25 Motor Nominal Speed [rpm]5-12 Terminal 27 Digital Input [0] No function*3-02 Minimum Reference [rpm]3-03 Maximum Reference [rpm]3-41 Ramp 1 Ramp-up Time [sec]3-42 Ramp 1 Ramp-down Time [sec]3-13 Reference Site1-29 Automatic Motor Adaptation (AMA) [1] Enable complete AMA* If no connection in terminal 27 is selected, noconnection to +24 V on terminal 27 necessary.Select Changes made to get information about:ï the last 10 changes. Use the up/down navigation keys to scroll between the last 10 changed parameters.ï the changes made since default setting.Select Loggings to get information about the display line readouts. The information is shown as graphs.Only display parameters selected in par. 0-20 and par. 0-24 can be viewed. It is possibleto store up to 120 samples in the memory for later reference." Main Menu ModeStart the Main Menu mode by pressing the[Main Menu] key. The readout shown to theright appears on the display.The middle and bottom sections on the display showa list of parameter groups which can be chosenby toggling the up and down buttons.130BP066.10Each parameter has a name and number which remain the same regardless of the programmingmode. In the Main Menu mode, the parameters are divided into groups. The first digit of theparameter number (from the left) indicates the parameter group number.All parameters can be changed in the Main Menu. However, depending on the choice of configuration(par. 1-00), some parameters canl be "missing". E.g. open loop hides all the P.I.D. parameters,and other enabled options make more parameter groups visible.142 MG.33.B6.22 - VLT is a registered Danfoss trademark