FC 300 Design GuideIntroduction to FC 300EMC Test Results (Emission, Immunity)The following test results have been obtained using a system with an adjustable frequency drive (with options ifrelevant), a shielded control cable, a control box with potentiometer, as well as a motor and motor cable.FC 301/FC 302 Conducted emission Radiated emission200-240 V380-500 V600 V no filterIndustrial environment Housing,tradesand lightindustriesIndustrialenvironmentHousing, tradesand lightindustriesSetup EN 55011Class A2EN 55011Class A1EN 55011Class BEN 55011Class A1EN 55011 Class BFC 301/FC 302 H20-3.7 kW 200-240 V0-7.5 kW 380-500 V16 ft (5 m)16 ft (5 m)NoNoNoNoNoNoNoNoFC 301 with integratedfilter H10-3.7 kW 200-240 V0-7.5 kW 380-480 V 246 (75 m)246 (75 m)164 ft (50m)164 ft (50m)33 ft (10 m)33 ft (10 m)YesYesNoNoFC 302 with integratedfilter H10-3.7 kW 200-240 V0-7.5 kW 380-500 V 490 ft (150 m)490 ft (150 m)490 ft (150m)490 ft (150m)130 ft (40 m)130 ft (40 m)YesYesNoNoFC 301 11-22 kW380-500 V 82 ft (25 m) No No No NoFC 302 11-22 kW380-500 V 82 ft (25 m) No No No NoFC 301 with integratedfilter H111-22 kW 380-500 V 246 (75 m)164 ft (50m) 33 ft (10 m) Yes NoFC 302 with integratedfilter H211-22 kW 380-500 V 490 ft (150 m)490 ft (150m) 130 ft (40 m) Yes NoHx is without filter42 MG.33.B6.22 - VLT is a registered Danfoss trademark