FC 300 Design GuideHow to Program" Parameters: Analog In/Out" 6-** Analog In/OutParameter group for configuring the analoginput and output." 6-0* Analog I/O ModeParameter group for setting up the analogI/O configuration.FC 300 is equipped with 2 analog inputs: Terminal53 and 54. The analog inputs on FC 302 canfreely be allocated to either voltage (-10 V - +10V) or current input (0/4 - 20 mA)NOTEThermistors may be connected to eitheran analog or a digital input.6-00 Live Zero Timeout TimeRange:1 - 99 s * 10sFunction:Enter the Live Zero Time-out time period. LiveZero Time-out Time is active for analog inputs, i.e.terminal 53 or terminal 54, allocated to currentand used as reference or feedback sources. If thereference signal value associated with the selectedcurrent input falls below 50% of the value set in par.6-10, par. 6-12, par. 6-20 or par. 6-22 for a timeperiod longer than the time set in par. 6-00, thefunction selected in par. 6-01 will be activated.6-01 Live Zero Timeout FunctionOption:*Off [0]Freeze Output [1]Stop [2]Jogging [3]Max. speed [4]Stop and trip [5]Function:Select the timeout function. The function set inpar. 6-01 will be activated if the input signal onterminal 53 or 54 is below 50% of the value in par.6-10, par. 6-12, par. 6-20 or par. 6-22 for a timeperiod defined in par. 6-00. If several timeoutsoccur simultaneously, the adjustable frequencydrive prioritizes the timeout functions as follows:1. Par. 6-01 Live Zero Timeout Function2. Par. 5-74 Encoder Loss Function3. Par. 8-04 Control word Timeout FunctionThe output frequency of the adjustablefrequency drive can be:The output frequency of the adjustablefrequency drive can be:ï [1] frozen at the present valueï [2] overruled to stopï [3] overruled to jog speedï [4] overruled to max. speedï [5] overruled to stop with subsequent tripThis parameter cannot be adjusted whilethe motor is running." 6-1* Analog Input 1Parameters for configuring the scaling and limitsfor analog input 1 (terminal 53).6-10 Terminal 53 Low VoltageRange:-10.0 - par. 6-11 * 0.07 VFunction:Enter the low voltage value. This analog inputscaling value should correspond to the minimumreference value, set in par. 3-02. See alsothe section Reference Handling.6-11 Terminal 53 High VoltageRange:Par. 6-10 to 10.0 V * 10.0V* default setting ( ) display text [ ] value for use in communication via serial communication port202 MG.33.B6.22 - VLT is a registered Danfoss trademark