FC 300 Design GuideFC 300 Selection" Relay Option MCB 105The MCB 105 option includes 3 pieces of SPDT contacts and must be fitted into option slot B.Electrical Data:Max terminal load (AC-1) 1) (Resistive load) ...................................................................... 240 V AC 2AMax terminal load (AC-15 ) 1) (Inductive load @ cosφ 0.4) .............................................. 240 V AC 0.2 AMax terminal load (DC-1) 1) (Resistive load) ....................................................................... 24 V DC 1 AMax terminal load (DC-13) 1) (Inductive load) ................................................................. 24 V DC 0.1 AMin terminal load (DC) ...................................................................................................... 5 V 10 mAMax switching rate at rated load/min load .................................................................... 6 min-1/20 sec -11) IEC 947 part 4 and 5When the relay option kit is ordered separately, the kit includes:ï Relay Module MCB 105ï Enlarged LCP fixture and enlarged terminal coverï Label for covering access to switches S201, S202, and S801ï Cable strips for fastening cables to relay moduleThe relay option does not support FC 302adjustable frequency drives manufacturedbefore week 50/2004.Min. software version: 2.03 (par. 15-43).IMPORTANT1. The label MUST be placed on the LCP frame as shown (UL-approved).Warning Dual supply79MG.33.B6.22 - VLT is a registered Danfoss trademark