VLT® AQUA Drive FC 202 N90K N110 N150 N160High/normal overload HO NO HO NO HO NO HO NO(High overload=150% current during 60 s.Normal overload=110% current during 60 s)Typical shaft output at 230 V [kW] 75 90 90 110 110 150 150 160Typical shaft output at 230 V [hp] 100 120 120 150 150 200 200 215Enclosure size D2h/D4hOutput current (3-phase)Continuous (at 230 V) [A] 240 302 302 361 361 443 443 535Intermittent (60 s overload) (at 230 V) [A] 360 332 453 397 542 487 665 589Continuous kVA (at 230 V) [kVA] 96 120 120 144 144 176 176 213Maximum input currentContinuous (at 230 V) [A] 231 291 291 348 348 427 427 516Maximum number and size of cables per phase- Mains, motor, brake, and load share [mm2 (AWG)] 2x185 (2x400 mcm) 2x185 (2x400 mcm) 2x185 (2x400 mcm) 2x185 (2x400 mcm)Maximum external mains fuses [A]1) 400 550 630 800Estimated power loss at 230 V [W]2), 3) 1990 2623 2613 3284 3195 4117 4103 5209Efficiency3) 0.97 0.97 0.97 0.97Output frequency [Hz] 0–590 0–590 0–590 0–590Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) 110 (230)Control card overtemperature trip [°C (°F)] 75 (167) 80 (176) 80 (176) 80 (176)Table 10.2 Electrical Data for Enclosures D2h/D4h, Mains Supply 3x200–240 V AC1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.2) Typical power loss is at normal conditions and expected to be within±15% (tolerance relates to variety in voltage and cable conditions). Thesevalues are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies todimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical controlcard power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options andcustomer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energyefficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.Specifications Operating GuideMG21A502 Danfoss A/S © 09/2018 All rights reserved. 9910 10