5.9 Control WiringAll terminals to the control cables are inside the drivebelow the LCP. To access the control terminals, either openthe door (D1h/D2h/D5h/D6h/D7h/D8h) or remove the frontpanel (D3h/D4h).5.9.1 Control Cable Routing• Isolate control wiring from high-powercomponents in the drive.• Tie down all control wires after routing them.• Connect shields to ensure optimum electricalimmunity.• When the drive is connected to a thermistor,ensure that the thermistor control wiring isshielded and reinforced/double insulated. A 24 VDC supply voltage is recommended.Fieldbus connectionConnections are made to the relevant options on thecontrol card. For more detail, see the relevant fieldbusinstruction. The cable must be tied down and routed alongwith other control wires inside the unit.5.9.2 Control Terminal TypesIllustration 5.35 shows the removable drive connectors.Terminal functions and default settings are summarized inTable 5.1 – Table 5.3.130BF144.10Illustration 5.35 Control Terminal Locations12 13 18 19 27 29 32 33 20 3739696861 42 50 53 54 55130BF145.101231 Serial communication terminals2 Digital input/output terminals3 Analog input/output terminalsIllustration 5.36 Terminal Numbers Located on the ConnectorsTerminal Parameter DefaultsettingDescription61 – – Integrated RC-filter forcable shield. ONLY forconnecting the shieldto correct EMCproblems.68 (+) Parametergroup 8-3* FCPort Settings– RS485 interface. Aswitch (BUS TER.) isprovided on thecontrol card for busterminationresistance. SeeIllustration 5.40.69 (-) Parametergroup 8-3* FCPort Settings–Table 5.1 Serial Communication Terminal DescriptionsDigital input/output terminalsTerminal Parameter DefaultsettingDescription12, 13 – +24 V DC 24 V DC supplyvoltage for digitalinputs and externaltransducers.Maximum outputcurrent 200 mA for all24 V loads.18 Parameter 5-10Terminal 18Digital Input[8] Start Digital inputs.19 Parameter 5-11Terminal 19Digital Input[10]Reversing32 Parameter 5-14Terminal 32Digital Input[0] Nooperation33 Parameter 5-15Terminal 33Digital Input[0] NooperationElectrical Installation Operating GuideMG21A502 Danfoss A/S © 09/2018 All rights reserved. 635 5