8.8 Wiring Configuration for a MotorThermistorNOTICEThermistors must use reinforced or double insulation tomeet PELV insulation requirements.Parameters130BB686.12VLT+24 V+24 VD IND IND INCOMD IND IND IN+10 VA INA INCOMA OUTCOM121318192027293233505354554239A53U - ID IN 37Function SettingParameter 1-90Motor ThermalProtection[2] ThermistortripParameter 1-93ThermistorSource[1] analoginput 53*=Default valueNotes/comments:If only a warning is wanted, setparameter 1-90 Motor ThermalProtection to [1] Thermistorwarning.Table 8.12 Wiring Configuration for a Motor Thermistor8.9 Wiring Configuration for a Relay Set-upwith Smart Logic ControlParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOMR1R212131819202729323337505354554239010203040506130BB839.10Function SettingParameter 4-30Motor FeedbackLoss Function[1] WarningParameter 4-31Motor FeedbackSpeed Error100 RPMParameter 4-32Motor FeedbackLoss Timeout5 sParameter 7-00 Speed PIDFeedback Source[2] MCB 102Parameter 17-11Resolution (PPR)1024*Parameter 13-00SL ControllerMode[1] OnParameter 13-01Start Event[19] WarningParameter 13-02Stop Event[44] Reset keyParameter 13-10ComparatorOperand[21] Warningno.Parameter 13-11ComparatorOperator[1] ≈ (equal)*Parameter 13-12ComparatorValue90Parameter 13-51SL ControllerEvent[22]Comparator 0Parameter 13-52SL ControllerAction[32] Set digitalout A lowParameter 5-40 Function Relay[80] SL digitaloutput A*=Default valueNotes/comments:If the limit in the feedback monitor is exceeded, warning 90,Feedback Mon. is issued. The SLC monitors warning 90, FeedbackMon. and if the warning becomes true, relay 1 is triggered.External equipment may require service. If the feedback errorgoes below the limit again within 5 s, the drive continues andthe warning disappears. Reset relay 1 by pressing [Reset] on theLCP.Table 8.13 Wiring Configuration for a Relay Set-up withSmart Logic ControlWiring Configuration Exampl... Operating GuideMG21A502 Danfoss A/S © 09/2018 All rights reserved. 778 8