11.2 International/North American Default Parameter SettingsSetting parameter 0-03 Regional Settings to [0] International or [1] North America changes the default settings for someparameters. Table 11.2 lists those parameters that are affected.Parameter International default parameter value North American default parameter valueParameter 0-03 Regional Settings International North AmericaParameter 0-71 Date Format DD-MM-YYYY MM/DD/YYYYParameter 0-72 Time Format 24 h 12 hParameter 1-20 Motor Power [kW] 1) 1)Parameter 1-21 Motor Power [HP] 2) 2)Parameter 1-22 Motor Voltage 230 V/400 V/575 V 208 V/460 V/575 VParameter 1-23 Motor Frequency 50 Hz 60 HzParameter 3-03 Maximum Reference 50 Hz 60 HzParameter 3-04 Reference Function Sum External/PresetParameter 4-13 Motor Speed High Limit[RPM]3)1500 RPM 1800 RPMParameter 4-14 Motor Speed High Limit [Hz]4) 50 Hz 60 HzParameter 4-19 Max Output Frequency 100 Hz 120 HzParameter 4-53 Warning Speed High 1500 RPM 1800 RPMParameter 5-12 Terminal 27 Digital Input Coast inverse External interlockParameter 5-40 Function Relay Alarm No alarmParameter 6-15 Terminal 53 High Ref./Feedb.Value50 60Parameter 6-50 Terminal 42 Output Speed 0-HighLim Speed 4-20 mAParameter 14-20 Reset Mode Manual reset Infinite auto resetParameter 22-85 Speed at Design Point[RPM]3)1500 RPM 1800 RPMParameter 22-86 Speed at Design Point [Hz] 50 Hz 60 HzParameter 24-04 Fire Mode Max Reference 50 Hz 60 HzTable 11.2 International/North American Default Parameter Settings1) Parameter 1-20 Motor Power [kW] is only visible when parameter 0-03 Regional Settings is set to [0] International.2) Parameter 1-21 Motor Power [HP] is only visible when parameter 0-03 Regional Settings is set to [1] North America.3) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [0] RPM.4) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [1] Hz.11.3 Parameter Menu StructureAppendix Operating GuideMG21A502 Danfoss A/S © 09/2018 All rights reserved. 14911 11