Power consumption and heat dissipationEMC provides the EMC Power Calculator to refine the power and heat figures to moreclosely match your array. Contact your EMC Sales Representative or use the EMCPower Calculator for specific supported configurations. The following table providescalculations of maximum power and heat dissipation.NOTICEPower consumption and heat dissipation details vary based on the number of systemand storage bays. Ensure that the installation site meets these worst caserequirements.Table 6 Power consumption and heat dissipationVMAX 250F VMAX 450F VMAX 850F VMAX 950FMaximum powerand heatdissipation at<26°C and>35°C aMaximumtotal powerconsumption<26°C />35°C(kVA)Maximumheatdissipation<26°C />35°C(Btu/Hr)Maximumtotal powerconsumption<26°C />35°C(kVA)Maximumheatdissipation<26°C />35°C(Btu/Hr)Maximumtotal powerconsumption<26°C />35°C(kVA)Maximumheatdissipation<26°C />35°C(Btu/Hr)Maximumtotal powerconsumption<26°C />35°C(kVA)Maximumheatdissipation<26°C />35°C(Btu/Hr)System bay 1Dual V-Brick4.13 / 5.19 14,090 /17,6986.69 / 9.05 22,813 /30,8616.94 / 9.30 23,665 /31,7137.25 / 9.61 24,712 /32,760System bay 2Dual V-BrickbN/A 6.28 / 8.38 21,415 /28,5766.49 / 8.59 22,131 /29,2926.80 / 8.90 23,178 /30,339a. Power values and heat dissipations shown at >35°C reflect the higher power levels associated with both the battery rechargecycle, and the initiation of high ambient temperature adaptive cooling algorithms. Values at <26°C are reflective of more steadystate maximum values during normal operation.b. Power values for system bay 2 and all subsequent system bays where applicable.SpecificationsPower consumption and heat dissipation 25