614-40096-00 184.2 LCD description① Load status and measurements② Equipment status icon③ Status / Message④ Battery statusAs default, or after 5 minutes of inactivity, the LCD displays the screen saver.The backlight LCD automatically dims after 5 minutes of inactivity. Press any button to restore the screen.Note. If other indicator appears, see troubleshooting page for additional information.The following table describes the status information provided by the UPS :Operation status Possible cause ActionStandby modeThe UPS is OFF, waiting for start-upcommand from userEquipment is not power until button is pressedduring start up and the green "normal mode" LEDindicator is illuminated.Normal modeThe UPS is operating normally. The UPS is powering and protecting the equipment.In AVR modeNo beepThe UPS is operating normally but theutility voltage is outside Normal modethresholds.The UPS is powering the equipment through theAutomatic Voltage Regulation device. The equipment isstill normally protected.On BatteryOne beep every 10secondsA utility failure has occurred and theUPS is in Battery mode.The UPS is powering the equipment with batterypower. Prepare your equipment for shutdown.End of backup time1 beep every 3secondsThe UPS is in Battery mode and thebattery is running low.This warning is approximate, and the actual time toshutdown may vary significantly. Depending on theUPS Load, the "Battery Low" warning may occur beforethe battery reaches 20% capacity remaining.