614-40096-00 24Submenu Available settings Default settings[DB9-7]: [On bat] [Low bat] [Bat fault] [UPS OK] [Loadprotected] [Load powered] [General alarm] [OVL pre-alarm][DB9-8]: [On bat] [Low bat] [Bat fault] [UPS OK] [Loadprotected] [Load powered] [General alarm] [OVL pre-alarm]Remotecommand[Yes] [No]If Enabled, shutdown or restart commands from softwareare authorized.[Yes]Shutdowncommands[Send CMD] [Output OFF] [OFF delay] [restart]Sets events or fault that will actuate Output signalparameters through external contact connector or RS232port[Send CMD]: [Yes] [No][Output OFF]: [No] [UPS] [Group 1][Group 2] [Group 1 + 2][OFF delay]: [0s] …[999s][Restart]: [Yes] [No]For a proper server shutdown please make sure that theOutput OFF delay is long enoughSend CMD: [No]Output OFF: [No]OFF delay: [0s]Restart: [Yes]On batterynotice delay[0s] ... [99s]Sets delay before providing an on battery notice tosoftware. [0s]Generalalarm[On battery] [Battery fault] [Overload pre-alarm] [Internalfault] [Ambient temp.] [Fan lock] [Current limit] [Shortcircuit] [Inverter overload] [Power overload] [Low battery][UPS OK] [Load protected] [Load powered]Defines which event or fault will generate a general alarmthrough Output signal screen.[Internal fault]Set CommCard IPv4[DHCP] : [Yes] [No][IP Adress] [Subnet mask] [Gateway]The UPS does not display the IPv4 settings menu bydefault, you can activate it by a communicationcommand.[Yes]XXX.XXX.XXX.XXX4.5 Communication ports