614-40096-00 23Submenu Available settings Default settingsRestart batt.level[0%] ... [100%]Automatic restart will occur only when the set percentageof battery charge is reached, and "Auto Restart" is enabledand set to ON. A setting of 0% allows immediate automaticrestart when utility returns after a UPS shutdown due toan extended power outage.[0%]Batterycharge mode [ABM® cycling] [Constant charge] [ABM® cycling]Externalbattery [Auto detection] [Manual EBM set.] [Manual battery set.][Auto detection]Using standard EBM, UPSautomatically detects thenumber of EBM connectedDeep disch.protect.[Enabled] [Disabled]If set to Enable, the UPS operates within the normal designrange of the battery during discharge.If set to Disable, the UPS allows deeper battery dischargeto extend battery runtime at the expense of long-termbattery life (warranty is also void if set to disable).[Enable]CommsettingsInput signals[ROO] [RPO] [DB9-4]Sets Input signals parameters (function, delay, operation)through external contact connectors or RS232 port.ROO port:- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdowncommands]- [Delay]: [0s] … [999s]- [Active]: [Open] [Closed]RPO port:- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdowncommands]- [Delay]: [0s] … [999s]- [Active]: [Open] [Closed]DB9-4 port:- [Function]: [No] [ROO] [RPO] [Building alarm][ShutdownCommands]- [Delay]: [0s] … [999s]- [Active]: [Low] [High]:[No][0s][Closed][No][0s][Open][No][0s][High]Outputssignals[Relay] [DB9-1] [DB9-7] [DB9-8]Sets events or fault that will actuate Output signalparameters through external contact connector or RS232port[Relay]: [On bat] [Low bat] [Bat fault] [UPS OK] [Loadprotected] [Load powered] [General alarm] [OVL pre-alarm][DB9-1]: [On bat] [Low bat] [Bat fault] [UPS OK] [Loadprotected] [Load powered] [General alarm] [OVL pre-alarm][Relay] : [Bat fault][DB9-1] : [Low bat][DB9-7] : [UPS OK][DB9-8] : [On bat]