INSTALLATIONEaton® 9130 UPS (700–3000 VA) User's Guide 164201718 Rev 3 www.eaton.com/powerquality 25Up to 1500 VA Models 2000–3000 VA ModelsFigure 10. Connecting the UPS Internal Batteries3. If you are installing EBMs, see the following section, “Connectingthe EBM(s),” before continuing with the UPS installation.4. Replace the UPS right front cover.To replace the cover, verify that the ribbon cable is protected and (ifEBMs are installed) the EBM cable is routed through the knockouton the bottom of the cover. Slide the cover to the left until it alignswith the left front cover. Reinstall the two screws on the right sideof the right front cover.5. If you are installing power management software, connect yourcomputer to one of the communication ports or optionalconnectivity card (see page 53). For the communication ports, usean appropriate cable (not supplied).6. If your rack has conductors for grounding or bonding of ungroundedmetal parts, connect the ground cable (not supplied) to the groundbonding screw. See “Rear Panels” on page 91 for the location ofthe ground bonding screw for each model.7. If an emergency power-off (disconnect) switch is required by localcodes, see “Remote Emergency Power-off” (REPO) on page 56 toinstall the REPO switch before powering on the UPS.8. Continue to “UPS Initial Startup” on page 34.