COMMUNICATIONEaton® 9130 UPS (700–3000 VA) User's Guide 164201718 Rev 3 www.eaton.com/powerquality 59Programmable Signal InputsThe UPS incorporates four programmable signal inputs: one RS-232input, two connectivity card inputs, and one REPO terminal input. SeeFigure 18 on page 53 for the locations of the ports. Configure the inputswith the “Signal Inputs” setting in “User Settings” on page 40.Table 6 shows the programmable settings for the signal inputs. Table 7shows the operation logic for the signal inputs.Table 6. Programmable Signal InputsSignal DescriptionNot Used The input operates only as a serial input (RxD) or has no function.Force Bypass If active, the UPS is forced to static bypass operation regardless ofthe bypass status.Remote Shutdown If active, the UPS output turns off after a user-defined remoteshutdown delay. The batteries continue charging. Inactive inputdoes not abort the shutdown countdown and does not cause theUPS to start up automatically.DelayedShutdown(and restart)If active, the UPS output turns off after a user-defined delayedshutdown delay. The batteries continue charging. Inactive inputdoes not abort the shutdown countdown but will cause the UPS tostart up automatically if the input voltage exists.On Generator If active, synchronization is disabled and the UPS transfers tobypass.Building Alarm 1 If active, the UPS generates the “Building Alarm 1” alarm.Table 7. Polarity OptionsInput DescriptionHigh Active state on high voltage (+Udc) levelLow Active state on low voltage (GND or -Udc) level