UPS MAINTENANCEEaton® 9130 UPS (700–3000 VA) User's Guide 164201718 Rev 3 www.eaton.com/powerquality64NOTE Leaveribbon cableconnected.Figure 23. Removing the UPS Right Front Cover2. Disconnect the internal battery connector (see Figure 24).3. Up to 1500 VA models only. If the EBM cable is not connected to anEBM, unclip the EBM cable and move it to the left out of the way.See Figure 24.Up to 1500 VA Models 2000–3000 VA ModelsInternal BatteryConnector Internal BatteryConnectorEBM CableBattery Cover Plate Battery Cover PlateFigure 24. Disconnecting the UPS Internal Batteries (Shown without EBMs)4. Grasp an edge of the battery cover plate and pull it forward gently.Remove and retain the battery cover plate. See Figure 24 for thelocation of the battery cover plate.