Voltage tolerance without transform-ers, (Rectifier input)380-415 V -15% / +20%440 V +/- 15%480 V -10% / +8%Voltage tolerance without transformers(Bypass input)-15% / +10%Rated input frequency 50 or 60 Hz, user configurableFrequency tolerance 40 to 72 HzNumber of input phases (rectifier & by-pass)3 phases + N + PE or3 phases + PE as an optionInput power factor 0.99Rated mains input currentMaximum mains input currentSee section11 and Table15Input current distortion at rated inputcurrent, iTHD30 kW: < 4,5%40-200 kW: < 3%Rectifier ramp-up, rectifier start andload step 10 A/s (default), configurable.Min 1A/sBackfeed protection Yes, for rectifier and bypass lines9.3 UPS system output9PHD 30-200 kW 9PHD 30-160 kW withincreased overload capabili-tyNumber of output phases 3 phases + N + PE or3 phases + PE as anoption3 phases + N + PE or3 phases + PE as anoptionRated output voltage 220/380 V; 230/400 V;240/415 V; 254/440;277/480 V, configurable.208–690 V available withoptional transformers220/380 V; 230/400 V;240/415 V; 254/440;277/480 V, configurable.208–690 V available withoptional transformersRated output frequency 50 or 60 Hz, userconfigurable50 or 60 Hz, userconfigurableTotal voltage harmonic dis-tortion:100 % linear load100 % non-linear load< 1%< 5%< 1%< 5%Eaton 9PHD UPS 30–200 kW User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Document ID: P-164000531 113 (127)