Input supplyline-to-line voltage [V]UPS rating [kW]30 40 50 80 100230 Phase cables 1 x 50 1 x 70 1 x 95 1 x 185 1 x 240Rectifier and by-pass fuse [A]125 160 200 315 400PE cable 1 x 25 1 x 35 1 x 50 1 x 95 1 x 120380 Phase cables 1 x 16 1 x 25 1 x 35 1 x 70 1 x 95Rectifier and by-pass fuse [A]63 80 100 160 200PE cable 1 x 16 1 x 16 1 x 16 1 x 35 1 x 50400 Phase cables 1 x 16 1 x 25 1 x 35 1 x 70 1 x 95Rectifier and by-pass fuse [A]63 80 100 160 200PE cable 1 x 16 1 x 16 1 x 16 1 x 35 1 x 50415 Phase cables 1 x 16 1 x 25 1 x 35 1 x 70 1 x 95Rectifier and by-pass fuse [A]63 80 100 160 200PE cable 1 x 16 1 x 16 1 x 16 1 x 35 1 x 50440 Phase cables 1 x 16 1 x 25 1 x 35 1 x 70 1 x 95Rectifier and by-pass fuse [A]63 80 100 160 200PE cable 1 x 16 1 x 16 1 x 16 1 x 35 1 x 50480 Phase cables 1 x 10 1 x 25 1 x 35 1 x 70 1 x 95Rectifier and by-pass fuse [A]50 80 100 160 200PE cable 1 x 10 1 x 16 1 x 16 1 x 35 1 x 50690 Phase cables 1 x 6 1 x 10 1 x 16 1 x 35 1 x 50Rectifier and by-pass fuse [A]40 50 63 100 125PE cable 1 x 6 1 x 10 1 x 16 1 x 16 1 x 25Table 10: Minimum recommended multi-core cable and fuse sizes for rectifier input andbypass input connection, 9PHD 120–200 kW UPSInput supplyline-to-line voltage [V]UPS rating [kW]120 150 160 200380 Phase cables 1 x 120 1 x 185 1 x 185 1 x 240Rectifier and bypassfuse [A]250 315 315 400PE cable 1 x 70 1 x 95 1 x 95 1 x 120Eaton 9PHD UPS 30–200 kW User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Document ID: P-164000531 51 (127)