11 AppendixNote: "NA" indicates that output transformer does not affect input values, andinput transformer does not affect output values.Note: In the "Combined" column, I indicates transformer input and Otransformer output.11.1Table 24: 20kW: Rated and maximum currents for rated power and voltage, fuse sizesRatedvoltage[V]Com-bined*Rectifier input Bypass input UPS out-putRatedcurrent[A]Maxi-mumcurrent[A]Fuse [A] Ratedcurrent[A]Fuse [A] Ratedcurrent[A]380 20_380 40 40 40 30 32 30400 20_400 38 40 40 29 32 29415 20_415 37 40 40 28 32 28440 20_440 34 34 63 26 32 26480 20_480 32 32 50 24 32 24208 20_208I 76 80 125 56 63 NA230 20_230I 69 72 125 50 63 NA380 20_380I 42 44 63 30 32 NA400 20_400I 39 42 63 29 32 NA415 20_415I 38 40 63 28 32 NA440 20_440I 36 38 63 26 32 NA480 20_480I 33 35 50 24 25 NA690 20_690I 23 24 40 17 20 NA208 20_208O NA NA NA NA NA 56230 20_230O NA NA NA NA NA 50380 20_380O NA NA NA NA NA 30400 20_400O NA NA NA NA NA 29415 20_415O NA NA NA NA NA 28440 20_440O NA NA NA NA NA 26480 20_480O NA NA NA NA NA 24690 20_690O NA NA NA NA NA 17Eaton 9PHD UPS 30–200 kW User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Document ID: P-164000531 118 (127)