Terminal TerminalfunctionPin Pin functionX12 Relay cardterminals(optional)X12:1 Relay K1 NCX12:2 Relay K1 returnX12:3 Relay K1 NOX12:4 Relay K2 NCX12:5 Relay K2 returnX12:6 Relay K2 NOX12:7 Relay K3 NCX12:8 Relay K3 returnX12:9 Relay K3 NOX12:10 Relay K4 NCX12:11 Relay K4 returnX12:12 Relay K4 NOX12:13 Relay K5 NCX12:14 Relay K5 returnX12:15 Relay K5 NOX12:16 Signal inputX12:17 Signal input returnX13 External parallelterminalsX13:1 External CAN highX13:2 External CAN lowX13:3 External CAN GNDX13:4 External CAN earthX13:5 External CAN terminationX13:6 External CAN termination returnX13:7 Pull chainX13:8 Pull chain returnNote: Do not connect relay contacts directly to the mains-related circuits(except the relay contacts of the industrial relay card X12). Reinforcedinsulation to the mains is required.When you are planning and performing the installation, make sure youunderstand the following notes:• All the interface wiring is provided by the operator.• When installing internal interface wiring to MiniSlot terminals, route the wiringthrough the conduits in the corner posts of the UPS.• All signal inputs or remote features require an isolated normally open (NO)contact or switch (rated at 24 VDC, 20 mA minimum) connected between thealarm input and the common terminal. All control wiring and relay and switchEaton 9PHD UPS 30–200 kW User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Document ID: P-164000531 80 (127)