38 OPERATION AND INSTALLATION INSTRUCTIONS MN280075EN July 2018Form 6 microprocessor-based rack-mount recloser controlThe Ethernet communication card accessory is offered in 3physical layer configurations (twisted pair and optical-fiberoptions) as shown in Table 15.Table 15 Ethernet communication card configurationsTypeCardConfigurationsOutputConnectorsCommunicationSpeed1 10/100 Base-T 2 * RJ-45 10 / 100MBps(auto switching)2 100 Base-FX(multi-mode fiber) 2 * MT-RJ 100MBps(full duplex)3 10/100 Base-T,100 Base-FX RJ-45 + MT-RJ 10/100MBpsand 100MBps4 100 Base-FX,(single-mode fiber) 2 * LC 100MBps(full duplex)Maximum link length is determined by the use of theparticular physical layer implementation, and can be furtherconstrained by the actual network configuration. In case ofthe 100Base-FX MT-RJ connector based implementation,maximum link length in excess of 2000m can be achievedwith 62.5/125μm multi mode fiber. The fiber-optic link uses1300nm wavelength, and can easily be interfaced to other100Base-FX solutions (ST connector patch cord solution).The Ethernet communication accessory card (Figure 32)is equipped with two physical ports configured to act asprimary and standby LAN connections. Availability of thebackup communication port enables creation of highlyredundant Ethernet networks thus increasing the overallsystem reliability.otee:N Under normal network conditions, allcommunications will be channeled through theprimary port (#1, Figure 32), with the standbyport either logically disabled, or configured for fastautomatic throw-over in case of the primary Ethernetlink failure. Refer to Service Information S280-70-4(ProView 4.X.X) or S280-70-21 (ProView 5.X.X) Form6 Control Programming Guide for additional Ethernetaccessory configuration information.TestingCAUTIONEquipment misoperation Do not connect this controlto an energized recloser until all control settings havebeen properly programmed and verified Refer to theprogramming information for this control Failure tocomply can result in control and recloser misoperation,equipment damage, and personal injury G110 3IMPORTANTThe Form 6 recloser control can be taken out of service fortesting and placed back into service without de-energizingits recloser and interrupting the system. However, duringthe time the control is out of service, the recloser isinoperative.Testing an installed controlThe following tests to determine initial operation of theForm 6 recloser control can be performed while connectedto an operating recloser.otee:N These are the only tests performed on an installed,operating control.1. Verify operating status of all indicator lights by pressingthe LAMP TEST key on the programming panel(Figure 33).2. Check the operational values for currents, voltages, andother metering information.METERINGRESETTARGETSEVENTSLAMP TESTMENUENTER+—SETTINGSOPERCOUNTERALARMSCHANGEF1 F2 F3 F4RS-232 DATA PORTLCD DisplayCursor MovementArrowsLAMP TEST KeyFigure 33 Lamp Test button, LCD display, and cursormovement arrowsotee:N Scroll through the LCD display messages by pressingthe and cursor movement arrows underneaththe LCD display on the programming panel(Figure 33).3. Verify the Control OK LED is illuminated on the controloperator panel (Figure 34). This indicates the presenceof DC power.otee:N The control includes a Power Save feature that willturn off the backlit LCD display and all LEDs if nofront panel keypad is pressed within ten minutes.Pressing any key will reactivate the display and LEDs.