44 OPERATION AND INSTALLATION INSTRUCTIONS MN280075EN July 2018Form 6 microprocessor-based rack-mount recloser controlFigure 40 Using a manual closing tool to operatethe recloserReturn the control to serviceWARNINGThis equipment is not intended to protect humanlife Follow all locally approved procedures and safetypractices when installing or operating this equipmentFailure to comply can result in death, severe personalinjury, and equipment damage G102 1After the required work or testing is completed, follow thisprocedure to return the control to service:CAUTIONEquipment misoperation Do not connect this controlto an energized recloser until all control settings havebeen properly programmed and verified Refer to theprogramming information for this control Failure tocomply can result in control and recloser misoperation,equipment damage, and personal injury G110 31. Verify that all control settings are correct prior toinstallation.WARNINGHazardous voltage Recloser and control mustbe solidly grounded Follow all locally approvedprocedures and safety practices when grounding thisequipment Improper grounding can result in contactwith high voltage, which will cause death or severepersonal injury G115 12. Connect the ground to the control.otee:N Refer to Grounding the control section.TB1123 5 7 9 11 13 15 17 194 6 8 10 12 14 16 18CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4CI4CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4TB3 1 3 5 7 9 11 13 15 17 19 21CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6TB42 4 6 8 10 12 14 16 18 20CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO61 3 5 7 9 11 13CO7 CO8 CO9 CO10 CO11 CO122 4 6 8 10 12CO7 CO8 CO9 CO10 CO11CO12FUSE(10 AMP)FUSE(10 AMP)TB5+1-52- 4+INPUT POWER AUXILIARY POWER28 VDCRECLOSER INTERFACE CONNECTIONSA1D3F5 72B4C6ETB6TB2 •1 2•3 4•5 6•7 8•9 10•11 12•13 14•15 16•17 18•19 20I(1-2) I(3-4) I(5-6) V(1-2) V(3-4) V(5-6) V1I(SEF)J1-RS-232IRIG-BRS-485RS-232 DTEC + –Figure 41 Back of Form 6 rack mount recloser control3. Use a screwdriver to re-connect all wiring on terminalblock TB2 (Voltage/Current Inputs) to the control(Figure 41).4. Connect any serial communications ports and IRIG-Btiming connection (Figure 41).5. Connect terminal block TB5 to the control by screwingthe mounting screw through each side of the terminalblock (Input Power) and into the control (Figure 41).6. Connect any control input and status output wiring toTB1, TB3, and TB4 (Figure 41).7. Connect terminal block TB6 to the control by screwingthe mounting screw through each side of the terminalblock (Recloser Interface Connections) and into thecontrol (Figure 41).8. Connect control AC sensing voltage to the control viadisconnect switches.otee:N Refer to Customer connections for DC power andAC voltage sensing section.9. Connect DC power to the control viadisconnect switches.otee:N Refer to Customer connections for DC power andAC voltage sensing section.