45OPERATION AND INSTALLATION INSTRUCTIONS MN280075EN July 2018Form 6 microprocessor-based rack-mount recloser controlCAUTIONHazardous voltage Open CT secondaries can generatehigh voltages Contact with CT pins of the disconnectedcable can cause electric shock and may result in personalinjury Open recloser contacts and open disconnectswitches before disconnecting control cable T204 310. Reconnect CT circuit by unshorting secondaries fromthe CT shorting-type terminal block.11. The recloser and control are ready for service. Onceinstalled, remove bypass switches on the recloser.12. Disable GND TRIP BLOCKED.A. Press the CHANGE button on the Operator Panelto enter the CHANGE mode.B. Depress the GND TRIP BLOCKED button withinten seconds after entering the CHANGE mode.otee:N If the GND TRIP BLOCK button is not depressedwithin ten seconds, the function is not activated.Additional informationCAUTIONThis equipment requires routine inspection andmaintenance to ensure proper operation If it is notmaintained, it can fail to operate properly Improperoperation can cause equipment damage and possiblepersonal injury G105 1Replacement kitsReplacement kits for the Form 6 recloser control areavailable through the factory Service Department. Toorder these kits, refer to the Replacement Parts pricelist for catalog numbers and pricing. Contact yourEaton representative for additional information andorder procedures.Factory-authorized service centersFactory-authorized service centers are located throughoutthe continental United States to provide maintenance,repair and testing services for Cooper Power seriescontrols and reclosers. For further information, contact yourEaton representative.Factory testing and troubleshooting classesThe factory service department offers a basic testing andtroubleshooting course for the Form 6 Microprocessor-Based Electronic Recloser Control. This course, taught byexperienced service technicians, is held at the factory’sin-house training facility. For additional information, contactyour Eaton representative.Type MET recloser control testerA 30-minute video program KSPV7 Type MET ElectronicRecloser Control Tester Operation and TestingProcedures is available as a supplemental training aid forservice personnel.