Power-up/reset conditionsWhen the system first comes up and no error conditionsare detected, the LCD displays the following message:Self-Test Complete.(Date/Time Shown)(PASS)If error conditions are detected, the LCD will display errormessage similar to those that follow:Self-Test Complete.Configuration ValueRequired!(ATTENTION...MORE )Self-Test Complete.Factory CalibrationRequired!(ATTENTION...MORE )Self-Test Complete.Data Acquisition!(FAILURE...MORE )If the “Configuration Value Required!” message appears,refer to Section 3: Initial control programming. Performbasic programming steps and then initiate a self-test.Self-Test Complete.Clock Needs Setting!(ATTENTION...MORE )Self-Test Complete.VR1 Input VoltageMissing!(ATTENTION...MORE )Self-Test Complete.VR1 Output VoltageMissing!(FAILURE...MORE )Self-Test Complete.VR1 No NeutralSync Signal!(ATTENTION...LAST)Consult Section 8: Troubleshooting or contact yourEaton representative for assistance with specific self-testmessages.Indication messagesThe fourth line of the LCD is used to provide messagesassociated with menu mode indications. These indicationmessages can be defined with up to 20 characters.Displayed during Self-Test message:• (PASS)• (ATTENTION)• (ATTENTION...MORE)• (ATTENTION...LAST)• (FAILURE)• (FAILURE...MORE)• (FAILURE...LAST)Displayed when an invalid function code is entered:• (INVALID FUNCTION)Displayed when and invalid security code is entered:• (INVALID SECURITY)Displayed when a parameter cannot be read, written,or reset because the proper security code has not beenentered:• (IMPROPER SECURITY)Displayed when setting a password that is too weak:• (PASSWORD TOO WEAK)Displayed when edit mode is active:• (EDIT)• (CONFIRM) (also displayed to prompt the user whenissuing a command from the menu system)Displayed when a value that has been entered is out thevalid range:• (VALUE TOO HIGH)• (VALUE TOO LOW)• (OUT OF RANGE)• (TIMEOUT)• (NEG ACKNOWLEDGE)• (INVALID DATE)• (INVALID TIME)Displayed when listing alarms or events:• (MORE...)• (LAST...)121INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225003EN April 2018CL-7 Voltage Regulator Control