Table 4 Programming for reverse power and additional featuresFunctioncode Description Instructions141 Regulator Identification FUNC, 141, ENTER, EDIT, Value, ENTERRequirements for Reverse Sensing Mode without IDPTs039 Source Voltage Calculation FUNC, 39, ENTER, EDIT Scroll - On; Off, ENTERRequired for Reverse Sensing Modes051 Reverse Set Voltage FUNC, 51, ENTER, EDIT, Value, ENTER052 Reverse Bandwidth FUNC, 52, ENTER, EDIT, Value, ENTER053 Reverse Time Delay FUNC, 53, ENTER, EDIT, Value, ENTER054 Reverse Line Drop Comp. Resistance FUNC, 54, ENTER, EDIT, Value, ENTER055 Reverse Line Drop Comp. Reactance FUNC, 55, ENTER, EDIT, Value, ENTER056 Reverse Sensing Mode FUNC, 56, ENTER, EDIT, Scroll - Locked Forward; Locked Reverse; Reverse Idle;Bi-directional; Neutral Idle; Co-generation; React Bi-directional, Bias Bi-directional,Bias Co-generation; Reverse Co-generation, ENTERRequired for Voltage Reduction Mode070 Voltage Reduction Mode FUNC, 70, ENTER, EDIT, Scroll - Off; Local/Digital Remote; Remote/Latch; Remote/Pulse,ENTER072 Local/Digital Reduction Value FUNC, 72, ENTER, EDIT, Value, ENTER073 Remote #1 Value FUNC, 73, ENTER, EDIT, Value, ENTER074 Remote #2 Value FUNC, 74, ENTER, EDIT, Value, ENTER075 Remote #3 Value FUNC, 75, ENTER, EDIT, Value, ENTER076 # of Pulse Reduction Steps FUNC, 76, ENTER, EDIT, Value, ENTER077 % of Voltage Red Per Pulse Step FUNC, 77, ENTER, EDIT, Value, ENTERRequired for Voltage Limit Mode080 Voltage Limit Mode FUNC, 80, ENTER, EDIT, Scroll - Off; High Limit Only; High/Low Limits, IVVC High Limit Only,IVVC High/Low Limit, ENTER081 High Voltage Limit FUNC, 81 ENTER, EDIT, Value, ENTER082 Low Voltage Limit FUNC, 82, ENTER, EDIT, Value, ENTERMulti-phase programmingWhen programming a control for multi-phase operation,there are a number of setting that configure the controlfor operation and a number that configure the controlto function with the connected voltage regulators. It isimportant to identify the pertinent settings applying to theindividual regulators and to the control and enter themcorrectly. Refer to Section 6: Control Features: Multi-phase voltage regulation and document MZ225003ENCL-7 Multi-phase Control Reference for guidance onprogramming the control for multi-phase operation.All of the basic control and regulator operational informationin this manual applies to controls and regulators whetherthey are in a single- or multi-phase configuration. Whenin the multi-phase configuration, the multi-phase LEDs(marked 1, 2 and 3), see Figure 13, can be used to identifyto which of the regulators the parameters apply. Whenprogramming the multi-phase control, pay attention to theLEDs to insure that the parameters are being entered forthe correct regulator. Pressing the forward arrow will cyclethe display through each of the connected regulators.Figure 13 Multi-phase LEDs and forward arrow20INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225003EN April 2018CL-7 Voltage Regulator Control