31 Amended: Jan 2014Reset to Factory SettingsThis feature will restore the panel to it’s factory settings, which on a programmed system iscatastrophic and not to be used lightly.The panel will go into Autolearn – losing all programming. It will also re-calibrate the screen and putthe default logo onto the screen.Sounder 1 & Sounder 2This menu allows the conventional sounder circuits to be set to continuous or pulsing, delayed ordouble knockTerminologyWhen the panel goes into Fire the word FIRE or ALARM can be selected to display this as part of theindication on the screen.Autolearn LockingThis feature has been added to prevent malicious or untrained personnel initiating an Autolearn oncethe system has been commissioned.Evacuate LockingEvacuate, once initiated from the panel menu or a programmed input, can operate ALL internal andexternal outputs connected to the loop. If the panel is controlling critical systems requiring a doubleknock scenario such as a Gas release system this could be immediately overridden by the evacuatecommand.In these instances evacuate would be considered inappropriate, therefore, evacuate can now belocked to prevent it overriding critical programming.Activate on EvacuateFIG 27This feature allows the user to further filter what is required to operate when Evacuate is not locked.