52 Amended: Jan 2014Power LED and touch screen illuminated but no text visibleWhen the panel is powered down the touch screen needs a minute to reset. Power the panel downand disconnect the batteries for 90 seconds, then re power the panel. If this does not work connectpanel comm and press the reset button. After a few seconds the PC should show debug codescrolling on the panel comm application. If it does not show debug text, ensure the micro board issecurely in place.If there is still no debug text the micro board or display PCB may need replacing. If debug text isshown on the PC the contrast may need adjusting on the micro board or either the micro board or thetouch screen may need replacing.Screen is visible but touch screen does not respond to touchEnsure the touch screen connector is in correctly.Ensure the micro board is securely attached to the display board.Send '7' from a PC to the panel to start the screen calibration routine.The touch screen works and is correctly calibrated but I cannot getto the supervisor entry screen.The panel may be in Swedish mode. If this is the case then to get access to the menu system theclass change input needs to be momentarily shorted.The access code entry screen will now be accessible.To disable Swedish mode on the panel, use the engineer level access code, select configure >program I/Oās and sounders > Auxiliary board. Swedish mode will be selected, press not requiredthen exit. The panel will now behave correctly.The general disabled LED is illuminatedIf this occurs something is disabled on the panel or a time delay has been programmed on the panel.To clear this use the 'enable all' button from the enable/disable menu in the supervisor access level.An alternative method, provided a delay has NOT been programmed then go to the enable disablemenu and instead of enabling all devices, go to enable disable I/O, and then disable the delays.