17INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.comSection 1: System installation and designOptional functions as per EN54 P2&4The Panel is Designed to the requirements to EN54 Parts 2 & 4 including all thefollowing options which can be selected as requiredPanel outputsPanel Sounders: (OPTION 7 8 EN54 PT 2)Two Sounder outputs are provided ONLY polarised equipment should be usedEnsure the polarity of the connections are observed at all times and end of linedevice are fitted for correct operationThe total alarm load across all sounder outputs = 1 5 AmpAll outputs are fused with 1 6 Amp Glass fuse Alarm devices should be spreadequally across the 2 sounder circuitsWARNINGDo not exceed the rated output currentOutput to fault warning routing equipment (Option 9 4 1C EN54 pt 2)This output, which is fused and monitored using 2k0 end of line resistor, is usedfor the transmission of fault signals to fault warning routing equipment This outputis monitored using 2k0 end of line resistor and it current limited to 30 mA Undernormal condition it operates by providing 12vdc which can be connected directly to a12v auxiliary device( relay) It is current limited to 30 mAUnder fault conditions or even if the Panel is powered down, this output will beswitch to O volts Ensure the polarity of the connections is observed at all times andend of line resistors ( 2K0 5% ) are fitted for correct operationDelays to outputs (Option 7 11 of EN54 pt 2)The Panel has the option to delay the operation of panel sounders, the fire routingequipment output and the fire protecting Equipment This delay is selectable usingthe site installer download software The delay is configurable in increments of 1minute up to a maximum of 10 minutes This delay can be enabled and disabled ataccess level 2The Panel has the facility for a specific call point to override this delay byprogramming this call point via an input interface to provide an evacuate signal usingsite InstallerCoincidence detection (Option 7 12 of EN54 pt 2)The Panel has the facility to inhibit the operation of the output sounders, Outputto Fire routing equipment and the output of the fire protecting equipment untilone more confirmatory signals are received from different zones This feature isprogrammable using Site Installer Software