25INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.comSection 1: System installation and designMaintainanceFunctions: See User Manual for full detailsDaily inspectionCheck that only the green “POWER ON” indicator shows Inspect for any faultindication Notify any faults to a system supervisiorWeekly testCheck indicatorsPress Supervisor mode on the top left of the touch screen Enter passcode Select“others” tab Press the button labeled weekly test, confirm you wish to perform thetest and the amber “System Test” LED will light The panel will stay in the weeklytest mode for 5mins before resetting During the weekly test, trigger a smokedetector or call point and check the fire panel registers the device and illuminatesthe correct zonal indicator Trigger a different device every time a weekly test isperformed ensuring devices are tested in rotation until all have been checked It isadvisable to develop a detailed a building plan highlighting devices and locations toaid testing The panel will reset automatically once the 5mins have elapsed If nodevices are triggered during the weekly test the panel will abort the test and resetafter 5mins Record weekly test in the table provided in this log bookQuarterlyCheck all previous log book entries and verify that remedial action has been takenCarry out the weekly test Visually examine the batteries and their connections, byloosening the screws behind printer door and opening the hinged front from the righthand sideDisconnect the mains supply and check that the battery is capable of supplying thealarm sounders, by operating a call pointAnnual testAs Weekly Test and Quarterly Test above Additionally test all sensors and call pointsand check operationEvery 2-3 yearsReplace or return the smoke detectors for cleaning to ensure correct operation andfreedom from false alarms Special equipment is required for cleaningsmoke detectorsEvery 5 yearsReplace sealed lead acid batteryCleaning: When cleaning the panel, use a moist cloth Do not use solvents orharsh abrasives