48 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.comSection 3: Panel controls & indicatorsViewing eventsTo activate the touch screen, touch the top left corner of the screen until the screenilluminates To enter the supervisor mode touch the supervisor button andenter the passcodeEnter the Supervisor Mode Passcode Select the “Others” tab and press View LogUse the scroll bar to view the list of upto 1000 eventsThe Panel event log stores up to 1000 events including, fires, faults, resets andaddress changes Once the maximum 1000 events has been reached Panel willautomatically overwrite the oldest event every time a new event is storedThe event log can only be reset by an approved service engineerEvacuate SilenceAlarmsMuteBuzzer ResetOthersEnable/DisableCheck `Config.PrintLamp TestPreAlarms Disabled FaultsWeekly TestView LogView FiresAC = 19SupervisorFRE offEvacuateOldestSilenceAlarmsShowFaultsMuteBuzzerShowFiresShowTestsResetExitNewestSupervisorFRE offShowAll002 FIRE! Lobby, [Optical] (Ana=150)Building 1, Ground floor, Panel 1, Loop 1, device 1001 Monday 13-Jan-2004 08:34:12Hard Reset003 Monday 06-Nov- 2000 11:22.56Soft Reset004 Monday 13-Nov-2001, 18:09.07 FaultPanel1, Loop 2 Zone 2, Address 5005 Monday 18-Feb-2001 22:20.18Mains or Battery failure