18 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.comSection 1: System installation and designAlarm counter (Option 7 13 of EN54 pt 2)The Panel has provision to record the number of instances that the CIE enters thefire alarm conditionThe information is available at access level 2TEST (Option 16 of EN54)The Panels equipped with the test option and can be implemented by eitherZone or AddressAlarm verificationThe Panel has the facility for global alarm verification where the detector alarmdecision is integrated over 30 secondsCable & wiringOnly the cable types listed below are allowable for loop connections1. Enhanced Fire TUF™2. Fire TUF™3. FP2004. MICCWhen choosing your preferred cable type, you must take note of the following cableand wiring requirements1. The cable must be 2 core screened with an over sheath2. Maximum loop length with any of the above cables is 2KM3. Maximum volt drop must be limited to 7 volts4. The conductors should be 1 5mm minimum5. Multicore cable should not be used for detector wiring6. Different loops should NEVER be run within the same cable7. Loop feeds and returns should never be used within the same cableCable resistanceCore diameter Typical FP200 resistance1.0mm² 18.1 Ohms/km/Core1.5mm² 12.1 Ohms/km/Core2.5mm² 7.41 Ohms/km/Core4.0mm² 4.61 Ohms/km/Core