InsulGard System Installation and Start Up Guideline33Appendix 3. PD Sensors Designation in DatabaseCommon rules for sensor designation in InsulGard database:1 - for upper switchgear cubical part2 - for bottom switchgear cubical part- omitted for non divided cubicalPhase: A, or B, or C, or N - for RFCT sensorinstalled on all three feeder shield ground wires- Switchgear cubical # counted from line left side- RTD-6 PD output #- can be omitted if applicableSensor Type:CC_ - IPDS sensorCT_ - RFCT sensorCTb - RFCT on bottle grounding wireRTm - RTD-6 PD sensor (new design)RTD - RTD-6 PD sensor (old design)C C _ 0 2 A 2Typically the InsulGard monitor comes preconfigured in accordance with available information on the application andthe configuration worksheet filled out at the time of order entry (see example below of PD sensor location on aswitchgear line). Switching InsulGard devices can require significant reprogramming of database software andInsulGard firmware settings and can lead to errors.InsulGard ID: SWG 72YJ573, VS #6InsulgardChannel #Sensor TypeCC – Coupling Capacitor (IPDS)CT- CT on cable shield groundCTb - CT on a bottle shieldground(Rule 1)CubiclePosition fromleft to right(Rule 2)Vertical Position1 for Top or2 for Bottomcompartment (ifapplicable)(Rule 2)Phase:CombinedSensorName(Rule 3)(Rule 4)(A / B / C/ N)1 CC 2 2 A CC_02 A22 CC 2 2 B CC_02 B23 CC 2 2 C CC_02 C24 CC 5 2 A CC_05 A25 CC 5 2 B CC_05 B26 CC 5 2 C CC_05 C27 CC 8 2 A CC_08 A28 CC 8 2 B CC_08 B29 CC 8 2 C CC_08 C210 CT 3 1 N CT_03 N111 CT 4 2 N CT_04 N212 CT 5 2 N CT_05 N213 CT 6 2 N CT_06 N214 CT 8 2 N CT_08 N215 CT 9 2 N CT_09 N2Sensor designations in this table indicate: type of the sensor (CC_ - IPDS) place of installation (02 – line up vertical section - cubicle position counted from left to right) bus or feeder phase (A), (For RFCT sensors (CT) installed on all three feeder shield ground wires its phasedesignated as N – neutral) part of the vertical section if applicable (2 - bottom part)