UPS OPERATING INSTRUCTIONSPower Xpert 9395 UPS (450–550 kVA) Installation and Operation Manual 164201701 Rev 4 www.eaton.com/powerquality7-207.3.16 Transfer from High Alert to Energy Saver ModeTo transfer the critical load to Energy Saver mode:NOTE The High Alert and Energy Saver mode commands are displayed only if enabled at the factory or byan Eaton Customer Service Engineer.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select GO TO ENERGY SAVER.5. Press the SELECT pushbutton on the UPS Command menu bar.The UPS transfers to Energy Saver mode and the critical load is immediatelysupplied by the bypass source. If the bypass source is not available, the powermodule remains on and an alarm sounds.The ONLINE status indicator is illuminated. The UPS status indicates ENERGYSAVER. The Bypass status indicates ON. The UPM status indicates ONLINE. Ifthe battery is not charging, the power module is off.7.3.17 Transfer from Online to Bypass Mode and Shut Down UPMsTo transfer the critical load to Bypass mode and shut down the UPMs:1. Transfer the critical load to bypass by performing the procedure inparagraph 7.3.5.2. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.3. On the System Status screen, select the UPM command. The UPS ControlCommand screen screen is displayed.4. On the UPS Control Command screen, select the UPM 1 command.5. Press the CONTROLS pushbutton on the UPS Control Command menu bar. TheUPM 1 Control Command screen is displayed.6. On the UPM 1 Control Command screen, select UPM OFF.7. Press the SELECT pushbutton on the UPM 1 Command menu bar.The UPM status indicates READY. The input, output, and battery contactorsopen, and the power module remains on.8. To turn off the power module, press the CONTROLS pushbutton on the UPSControl Command menu bar. The UPM 1 Control Command screen is displayed.9. On the UPM 1 Control Command screen, select UPM OFF.