UPS OPERATING INSTRUCTIONSPower Xpert 9395 UPS (450–550 kVA) Installation and Operation Manual 164201701 Rev 4 www.eaton.com/powerquality 7-357.4.14 Transfer from High Alert to Bypass ModeTo transfer the critical load to Bypass mode:NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton CustomerService Engineer.1. On any UPS, press the CONTROLS pushbutton on the main menu bar. The SystemStatus screen is displayed.2. On the System Status screen, select the BYPASS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The BypassControl Command screen is displayed.4. On the Bypass Control Command screen, select GO TO BYPASS.5. Press the SELECT pushbutton on the Bypass Command menu bar.All of the UPSs transfer to Bypass mode and the critical load is immediatelysupplied by the bypass source. If the bypass source is not available, the powermodule remains on and an alarm sounds.The BYPASS status indicator is illuminated. The UPS status indicates BYPASS. TheBypass status indicates ON. The UPM status indicates READY. The powermodule remains on.7.4.15 Transfer from Energy Saver to High Alert ModeTo transfer the critical load to High Alert mode:NOTE The Energy Saver and High Alert mode commands are displayed only if enabled at the factory or byan Eaton Customer Service Engineer.1. On any UPS, press the CONTROLS pushbutton on the main menu bar. The SystemStatus screen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select GO TO HIGH ALERT.5. Press the SELECT pushbutton on the UPS Command menu bar.All of the UPSs transfer to Battery mode and then to High Alert mode. After onehour the UPSs transfer to Energy Saver mode and the critical load is immediatelysupplied by the bypass source. If the bypass source is not available, the powermodule remains on and an alarm sounds.The ONLINE status indicator is illuminated. The UPS status indicates HIGHALERT. The UPM status indicates ONLINE. The power module is on.