INSTALLATIONEATON Power Distribution Rack (208V) User’s Guide 164201720 Rev 1 www.powerware.com24C A U T I O NBe absolutely sure there is no power.9. Dual 800A Main Input Lug, Dual 400A Main Input Breaker, and Dual 600A Main InputBreaker configurations. Connect the neutral cables to the neutral busbars (seeFigure 13, and Table 2 and Table 3 on page 19):If ordered, locate the two supplied neutral CTs (labeled N") hanging at the baseof the panelboard mounting plate. Cut the tie−wraps to remove the CTs from theplate but DO NOT detach the blue and white wiring connecting each CT to thecabinet.If ordered, install one neutral CT on the neutral cable for the first side. Secure theCT to the cable with tie−wraps (not supplied).Connect the neutral cable for the first side to its neutral busbar.Repeat for the second side’s neutral CT (if ordered) and neutral connection.NFactory Location of CTs for Customer InstallationNOTE Neutral CTs are optional.Panelboard MountingPlateNeutral CT (optional) ShownInstalled on Neutral CableBlue/White WiringCut tie−wraps to removeCTs from plate. DO NOTdetach blue/whitewiring.Neutral BusbarFigure 13. Installing the Neutral ( Dual 800A Main Input Lug, Dual 400A Main Input Breaker, and Dual 600A Main Input Breaker )NOTE Figure 13 shows top entry wiring, optional neutral CTs for measured neutral current, and frontaccess installation.