48 InStALLAtIon And opErAtIon mAnuAL 25-13741-E January 2020 www.eaton.com11. Commissioning6. Go to option ‘Accept’ at the end of the list. Re-confirm the system configuration.7. Outstations are now addressed. Outstations would now be able to communicatewith panel.8. An error message will be displayed if auto learn process is not successful due toany failure – eg: No OS connected, Loop break etc.9. Correct the condition and perform the learn until successful.trouBLESHootInG: If any of the wiring is not correct, the number of outstationsdetected will be incorrect. Fault Log / Learn status can be referred to identify theproblem. After fixing the issue, perform the Outstation learn process again.ote:n Outstation Learn process must be performed whenever an Outstation hasbeen added, removed or replaced in an existing system or details are changedfor any Outstation. The system will prompt the installer to keep the namesand locations of all existing outstations, or overwrite / delete them.ote:n Two options are added as sub menu under ‘Install’ once learn is successful -Webserver, Config. Backup / Restore.4 Outstations FoundAccept04: Type B V1.01SN: 13598478734 Outstations FoundAccept04: Type B V1.01SN: 1359847873Outstation Learn OKOK =