5-34 B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5PARAMETERRange: Indicator 1...Indicator 96Default: Indicator 1...Indicator 96Read-only field. Up to 96 windows are possible.CONTENTRange: Actual, Alarm, MixedDefault: AlarmSelect if the cell is to be an alarm, an actual value, or a combination thereof, for example consists of a single meteredvalue (set to “Actual”), contains a single alarm indication (set to “Alarm”), or contains both a metered value and an alarmindication (set to “Mixed”).ALARM INPUTRange: OFF, ON, any FlexLogic operandDefault: OFFSelect a trigger for the alarm, or the input signal connected to the alarm. For example, when set to "FIRST ETHERNETFAIL" and the Ethernet connection on port 1 goes down, the alarm is triggered. The field is read-only for an actual value.The options displayed for selection are the FlexLogic operands specific to the product.ALARM TYPERange: Acknowledgeable, Self Reset, LatchedDefault: AcknowledgeableSet the alarm type. The field is read-only for an actual value.Acknowledgeable — Follow the state transitions, as outlined in the Annunciator section of the Interfaces chapter.Self Reset — Track the state of the input operand. The alarm turns on when the trigger activates and off when the triggerclears.Latched — Alarm remains latched and can be reset using the RESET button.To acknowledge/reset/unlatch an alarm, use the arrow buttons on the graphical front panel and press the Enter button.TEXT (LINE 1 to 3)Range: up to 10 alphanumeric charactersDefault:The text that displays in the annunciator cell, over three lines. Three lines can be displayed. Note that a specifiedmetering value replaces the text for the selected line. This means that a line can display text or be set to show an actualmetered value. If the text does not display it is because an actual metered value is over-riding it; change the line for thetext or for the actual value.TEXT COLORRange: 24-bit color selectorDefault: WhiteThe color to display any of the three text or actual value lines specified.BACK COLORRange: 24-bit color selectorDefault: RedThe background color to display for any triggered cell, for example when alarm is triggered.ConfigureRange: ConfigureDefault: ConfigureThe Configure button becomes active when the CONTENT field is set to "Actual" or "Mixed." The window configuresmetered values.