5-230 C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 5: SETTINGS5TRIP BUS 1 RESET DELAY — This setting specifies a time delay to reset an output command. Set the time delay long enoughto allow the breaker or contactor to perform a required action.TRIP BUS 1 INPUT 1 to TRIP BUS 1 INPUT 16 — These settings select a FlexLogic operand to be assigned as an input to the tripbus.TRIP BUS 1 LATCHING — This setting enables or disables latching of the trip bus output. This is typically used when lockout isrequired or user acknowledgement of the relay response is required.TRIP BUS 1 RESET — The trip bus output is reset when the operand assigned to this setting is asserted. Note that the RESET OPoperand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or viacommunications resets the trip bus output.Figure 5-123: Trip bus logic5.8.3 Setting groupsSETTINGS CONTROL ELEMENTS SETTING GROUPS SETTING GROUPS SETTING GROUPSFUNCTION: EnabledRange: Disabled, Enabled SETTING GROUPS BLK:OffRange: FlexLogic operand GROUP 2 ACTIVATE ON:OffRange: FlexLogic operand GROUP 6 ACTIVATE ON:OffRange: FlexLogic operand GROUP 1 NAME: Range: up to 16 alphanumeric characters GROUP 6 NAME: Range: up to 16 alphanumeric characters