6-16 C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUALMETERING CHAPTER 6: ACTUAL VALUES66.4.2 Sources6.4.2.1 MenuACTUAL VALUES METERING SOURCE SRC 1This menu displays the metered values available for each source.Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignmentsfor this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and powervalues are unavailable.6.4.2.2 Phase current meteringACTUAL VALUES METERING SOURCE SRC 1 PHASE CURRENT SOURCE SRC 1 PHASE CURRENT SRC 1See below GROUND CURRENT SRC 1See page 6-17 PHASE VOLTAGE SRC 1See page 6-17 AUXILIARY VOLTAGE SRC 1See page 6-18 POWER SRC 1See page 6-18 ENERGY SRC 1See page 6-19 DEMAND SRC 1See page 6-19 FREQUENCY SRC 1See page 6-20 PHASE CURRENT SRC 1 SRC 1 RMS Ia: 0.000b: 0.000 c: 0.000 A SRC 1 RMS Ia:0.000 A SRC 1 RMS Ib:0.000 A SRC 1 RMS Ic:0.000 A SRC 1 RMS In:0.000 A SRC 1 PHASOR Ia:0.000 A 0.0° SRC 1 PHASOR Ib:0.000 A 0.0° SRC 1 PHASOR Ic:0.000 A 0.0° SRC 1 PHASOR In:0.000 A 0.0° SRC 1 ZERO SEQ I0:0.000 A 0.0°