5-28 F60 Feeder Protection System GE Multilin5.2 PRODUCT SETUP 5 Z SETTINGS5To set up a F60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, thefollowing dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and“GGIO3.ST.Ind2.stVal”. The F60 will then create a dataset containing these two data items. The Boolean status values fromthese data items can be utilized as remote input FlexLogic™ operands. First, the REMOTE DEVICE 1(16) DATASET settingmust be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then REMOTE IN 1(16) ITEM settingsmust be set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic™ operands will then change state inaccordance with the status values of the data items in the configured dataset.Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-instantaneous) values can be transmitted. Received values are used to populate the GGIO3.XM.AnIn1 and higher items.Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up).The main menu for the IEC 61850 server configuration is shown below.PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ SERVER CONFIGURATIONThe IED NAME and LD INST settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logicalnodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The LOCATION is avariable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS connections. The INCLUDENON-IEC DATA setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be“Disabled”.The SERVER SCANNING feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If theGOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabledto increase CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta-tus values in the F60. Clients will still be able to connect to the server (F60 relay), but most data values will not be updated.This setting does not affect GOOSE/GSSE operation.Changes to the IED NAME setting, LD INST setting, and GOOSE dataset will not take effect until the F60 is restarted. SERVER CONFIGURATIONIED NAME: IECDevice Range: up to 32 alphanumeric charactersMESSAGE LD INST: LDInst Range: up to 32 alphanumeric charactersMESSAGE LOCATION: Location Range: up to 80 alphanumeric charactersMESSAGE IEC/MMS TCP PORTNUMBER: 102Range: 1 to 65535 in steps of 1MESSAGE INCLUDE NON-IECDATA: EnabledRange: Disabled, EnabledMESSAGE SERVER SCANNING:DisabledRange: Disabled, EnabledNOTE