GE Multilin F60 Feeder Protection System B-15APPENDIX B B.4 MEMORY MAPPINGB21AA Breaker flashover 1 status closed B 0 to 65535 --- 1 F300 021AB Breaker flashover 1 status closed C 0 to 65535 --- 1 F300 021AC Breaker flashover 1 voltage pickup level 0 to 1.5 pu 0.001 F001 85021AD Breaker flashover 1 voltage difference pickup level 0 to 100000 V 1 F060 100021AF Breaker flashover 1 current pickup level 0 to 1.5 pu 0.001 F001 60021B0 Breaker flashover 1 pickup delay 0 to 65.535 s 0.001 F001 10021B1 Breaker flashover 1 supervision phase A 0 to 65535 --- 1 F300 021B2 Breaker flashover 1 supervision phase B 0 to 65535 --- 1 F300 021B3 Breaker flashover 1 supervision phase C 0 to 65535 --- 1 F300 021B4 Breaker flashover 1 block 0 to 65535 --- 1 F300 021B5 Breaker flashover 1 events 0 to 1 --- 1 F102 0 (Disabled)21B6 Breaker flashover 1 target 0 to 2 --- 1 F109 0 (Self-Reset)21B7 Reserved (4 items) --- --- --- F001 021BB ...Repeated for breaker flashover 2 0 to 99999999 kA2 -cyc 1 F060 0Breaker Arcing Current Actuals (Read Only Non-Volatile) (2 modules)21E0 Breaker 1 Arcing Current Phase A 0 to 99999999 kA2 -cyc 1 F060 021E2 Breaker 1 Arcing Current Phase B 0 to 99999999 kA2 -cyc 1 F060 021E4 Breaker 1 Arcing Current Phase C 0 to 99999999 kA2 -cyc 1 F060 021E6 Breaker 1 Operating Time Phase A 0 to 65535 ms 1 F001 021E7 Breaker 1 Operating Time Phase B 0 to 65535 ms 1 F001 021E8 Breaker 1 Operating Time Phase C 0 to 65535 ms 1 F001 021E9 Breaker 1 Operating Time 0 to 65535 ms 1 F001 021EA ...Repeated for Breaker Arcing Current 2Breaker Arcing Current Commands (Read/Write Command) (2 modules)2224 Breaker 1 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)2225 Breaker 2 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)Passwords Unauthorized Access (Read/Write Command)2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)Hi-Z (High Impedance Fault Detection) Commands (Read/Write Command)2240 Hi-Z Clear Oscillography 0 to 1 --- 1 F126 0 (No)2241 Hi-Z Oscillography Force Trigger 0 to 1 --- 1 F126 0 (No)2242 Hi-Z Oscillography Force Algorithm Capture 0 to 1 --- 1 F126 0 (No)2243 Hi-Z Reset Sigma Values 0 to 1 --- 1 F126 0 (No)Hi-Z (High Impedance Fault Detection) Status (Read Only)2250 Hi-Z Status 0 to 9 --- 1 F187 0 (NORMAL)2251 Hi-Z Phase A Arc Confidence 0 to 100 1 F001 02252 Hi-Z Phase B Arc Confidence 0 to 100 1 F001 02253 Hi-Z Phase C Arc Confidence 0 to 100 1 F001 02254 Hi-Z Neutral Arc Confidence 0 to 100 --- 1 F001 0Hi-Z (High Impedance Fault Detection) Records (Read Only) (4 modules)2260 Hi-Z Capture 1 Trigger Type 0 to 6 --- 1 F188 0 (NONE)2261 Hi-Z Capture 1 Time 0 to 1 --- 1 F050 02263 ...Repeated for Hi-Z Capture 22266 ...Repeated for Hi-Z Capture 32269 ...Repeated for Hi-Z Capture 4Hi-Z (High Impedance Fault Detection) RMS Records (Read Only) (4 modules)2270 Hi-Z RMS Capture 1 Trigger Type 0 to 6 --- 1 F188 0 (NONE)2271 Hi-Z RMS Capture 1 Time 0 to 1 --- 1 F050 02273 ...Repeated for Hi-Z RMS Capture 22276 ...Repeated for Hi-Z RMS Capture 32279 ...Repeated for Hi-Z RMS Capture 4Fault Location (Read Only) (5 modules)2340 Fault 1 Prefault Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 02342 Fault 1 Prefault Phase A Current Angle -359.9 to 0 degrees 0.1 F002 0Table B–9: MODBUS MEMORY MAP (Sheet 7 of 55)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT