GE Multilin F60 Feeder Protection System B-25APPENDIX B B.4 MEMORY MAPPINGBPower System (Read/Write Setting)4600 Nominal Frequency 25 to 60 Hz 1 F001 604601 Phase Rotation 0 to 1 --- 1 F106 0 (ABC)4602 Frequency And Phase Reference 0 to 5 --- 1 F167 0 (SRC 1)4603 Frequency Tracking Function 0 to 1 --- 1 F102 1 (Enabled)Incipient cable fault detector (read/write settings)46B2 Incipient cable fault detector 1 function 0 to 1 --- 1 F102 0 (Disabled)46B3 Incipient cable fault detector 1 block 0 to 65535 --- 1 F300 046B4 Incipient cable fault detector 1 source 0 to 5 --- 1 F167 0 (SRC 1)46B5 Incipient cable fault detector 1 pickup 0.1 to 10 pu 0.01 F001 5046B6 Incipient cable fault detector 1 mode 0 to 1 --- 1 F254 0 (Number of Counts)46B7 Incipient cable fault detector 1 counts 1 to 10 --- 1 F001 246B8 Incipient cable fault detector 1 time window 0 to 1000 s 0.01 F003 100046BA Incipient cable fault detector 1 reset delay 0 to 65.535 s 0.001 F001 10046BB Incipient cable fault detector 1 target 0 to 2 --- 1 F109 0 (Self-reset)46BC Incipient cable fault detector 1 events 0 to 1 --- 1 F102 0 (Disabled)46BD ...Repeated for incipient cable fault detector 2Breaker control (read/write settings)4700 Breaker 1 function 0 to 1 --- 1 F102 0 (Disabled)4701 Breaker 1 name --- --- --- F206 “Bkr 1"4704 Breaker 1 mode 0 to 1 --- 1 F157 0 (3-Pole)4705 Breaker 1 open 0 to 65535 --- 1 F300 04706 Breaker 1 close 0 to 65535 --- 1 F300 04707 Breaker 1 phase A / three-pole closed 0 to 65535 --- 1 F300 04708 Breaker 1 phase B closed 0 to 65535 --- 1 F300 04709 Breaker 1 phase C closed 0 to 65535 --- 1 F300 0470A Breaker 1 external alarm 0 to 65535 --- 1 F300 0470B Breaker 1 alarm delay 0 to 1000000 s 0.001 F003 0470D Breaker 1 pushbutton control 0 to 1 --- 1 F102 0 (Disabled)470E Breaker 1 manual close recall time 0 to 1000000 s 0.001 F003 04710 Breaker 1 out of service 0 to 65535 --- 1 F300 04711 Breaker 1 block open 0 to 65535 --- 1 F300 04712 Breaker 1 block close 0 to 65535 --- 1 F300 04713 Breaker 1 phase A / three-pole opened 0 to 65535 --- 1 F300 04714 Breaker 1 phase B opened 0 to 65535 --- 1 F300 04715 Breaker 1 phase C opened 0 to 65535 --- 1 F300 04716 Breaker 1 operate time 0 to 2 s 0.001 F001 704717 Breaker 1 events 0 to 1 --- 1 F102 0 (Disabled)4718 Reserved --- --- --- --- ---4719 ...Repeated for breaker 2Synchrocheck (Read/Write Setting) (2 modules)47A0 Synchrocheck 1 Function 0 to 1 --- 1 F102 0 (Disabled)47A1 Synchrocheck 1 V1 Source 0 to 5 --- 1 F167 0 (SRC 1)47A2 Synchrocheck 1 V2 Source 0 to 5 --- 1 F167 1 (SRC 2)47A3 Synchrocheck 1 Maximum Voltage Difference 0 to 400000 V 1 F060 1000047A5 Synchrocheck 1 Maximum Angle Difference 0 to 100 degrees 1 F001 3047A6 Synchrocheck 1 Maximum Frequency Difference 0 to 2 Hz 0.01 F001 10047A7 Synchrocheck 1 Dead Source Select 0 to 5 --- 1 F176 1 (LV1 and DV2)47A8 Synchrocheck 1 Dead V1 Maximum Voltage 0 to 1.25 pu 0.01 F001 3047A9 Synchrocheck 1 Dead V2 Maximum Voltage 0 to 1.25 pu 0.01 F001 3047AA Synchrocheck 1 Live V1 Minimum Voltage 0 to 1.25 pu 0.01 F001 7047AB Synchrocheck 1 Live V2 Minimum Voltage 0 to 1.25 pu 0.01 F001 7047AC Synchrocheck 1 Target 0 to 2 --- 1 F109 0 (Self-reset)47AD Synchrocheck 1 Events 0 to 1 --- 1 F102 0 (Disabled)Table B–9: MODBUS MEMORY MAP (Sheet 17 of 55)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT