GE Multilin F60 Feeder Protection System 3-473 HARDWARE 3.4 MANAGED ETHERNET SWITCH MODULES3The wiring for the managed Ethernet switch module is shown below.Figure 3–50: MANAGED ETHERNET SWITCH MODULE WIRING3.4.3 MANAGED SWITCH LED INDICATORSThe 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FXports have one LED to indicate linkup and activity.Figure 3–51: ETHERNET SWITCH LED INDICATORS3.4.4 INITIAL SETUP OF THE ETHERNET SWITCH MODULEa) DESCRIPTIONUpon initial power up of a F60 device with an installed Ethernet switch, the front panel trouble LED will be illuminated andthe ENET MODULE OFFLINE error message will be displayed. It will be necessary to configure the Ethernet switch and thenplace it online. This involves two steps:1. Configuring the network settings on the local PC.2. Configuring the F60 switch module through EnerVista UR Setup.These procedures are described in the following sections. When the F60 is properly configured, the LED will be off and theerror message will be cleared.$&'5%DVH);%DVH);7[ 5[7[ 5[*5281'³:D:E:D3RZHUVXSSO\&RSSHUSRUWV&38 6700ILEHURSWLFFDEOH00ILEHURSWLFFDEOH%DVH7%DVH7%DVH);7[ 5[%DVH);7[ 5[)LEHUSRUWV00ILEHURSWLFFDEOH00ILEHURSWLFFDEOH²%DVH7FDEOH%DVH7FDEOHWR9'&WR9$&842868A2.CDRConnection speed indicator (OFF = 10 Mbps; ON = 100 Mbps)Link indicator (ON = link active; FLASHING = activity)Duplex mode indicator (OFF = half-duplex; ON = full-duplex)Link indicator (ON = link active; FLASHING = activity)