GE Multilin F60 Feeder Protection System 5-295 SETTINGS 5.2 PRODUCT SETUP5The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset itemsfor reception:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION RECEPTION CONFIGURABLE GOOSE CONFIGURABLE GOOSE 1(16) CONFIG GSE 1(32) DATA ITEMSThe configurable GOOSE settings allow the F60 to be configured to receive a number of different datasets within IEC61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful forintercommunication between F60 IEDs and devices from other manufacturers that support IEC 61850.For intercommunication between F60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-tains the same DNA and UserSt bit pairs that are included in GSSE messages.To set up a F60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, thefollowing dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and“GGIO3.ST.Ind2.stVal”. The F60 will then create a dataset containing these two data items. The Boolean status values fromthese data items can be utilized as remote input FlexLogic™ operands. First, the REMOTE DEVICE 1(16) DATASET settingmust be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then REMOTE IN 1(16) ITEM settingsmust be set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic™ operands will then change state inaccordance with the status values of the data items in the configured dataset.Double-point status values may be included in the GOOSE dataset. Received values are populated in theGGIO3.ST.IndPos1.stVal and higher items.Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.Received values are also available as FlexAnalog™ parameters (GOOSE analog In1 and up).GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.The main menu for the IEC 61850 server configuration is shown below.PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL SERVER CONFIGURATION CONFIG GSE 1 DATASET ITEMSITEM 1:GGIO3.ST.Ind1.stValRange: all valid MMS data item references fortransmitted dataMESSAGE ITEM 2:GGIO3.ST.IndPos1.stVRange: all valid MMS data item references fortransmitted dataMESSAGE ITEM 3:NoneRange: all valid MMS data item references fortransmitted data↓MESSAGE ITEM 32:NoneRange: all valid MMS data item references fortransmitted data SERVER CONFIGURATIONIED NAME: IECDevice Range: up to 32 alphanumeric charactersMESSAGE LD INST: LDInst Range: up to 32 alphanumeric charactersMESSAGE LOCATION: Location Range: up to 80 alphanumeric charactersMESSAGE IEC/MMS TCP PORTNUMBER: 102Range: 1 to 65535 in steps of 1MESSAGE INCLUDE NON-IECDATA: EnabledRange: Disabled, EnabledMESSAGE SERVER SCANNING:DisabledRange: Disabled, EnabledNOTE