C-12 F60 Feeder Protection System GE MultilinC.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP APPENDIX CCC.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP C.5.1 OVERVIEWThe F60 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.1. An ICD file is generated for the F60 by the EnerVista UR Setup software that describe the capabilities of the IED.2. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-dors) for system configuration.3. The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settingsfile(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.The configuration process is illustrated below.Figure C–1: IED CONFIGURATION PROCESSThe following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC61850:• BDA: Basic Data Attribute, that is not structured• DAI: Instantiated Data Attribute• DO: Data Object type or instance, depending on the context842790A1.CDREthernetSystem configuratorSCD fileSystem specification tool SSD fileSystemspecification dataICD file 2Process ofcreating ICD(vendor 2)Creating ICD (GE Multilin)EnerVistaUR SetupICD file 1IED (UR-series)ORICD file 3 ICD file NUR relay 1Updating IED with new configuration (GE Multilin)EnerVista UR SetupVendor relay 2 Vendor relay 3 Vendor relay NSetting files(.URS)IEC 61850 relatedconfiguration for theIED (GSSE/GOOSE,server, logical nodeprefixes, MMXUdeadbands, GGIO2control, etc.)ImportURS 1 URS 2 URS XWrite settingsfile to deviceWrite settings fileto other devicesVendor specific toolfor updating newconfiguration to IED(vendor 2)Vendor specific toolfor updating newconfiguration to IED(vendor 3)System Configuration(network, cross-communications, IED settingmodification, etc.)Process ofcreating ICD(vendor 3)Process ofcreating ICD(vendor )NVendor specific toolfor updating newconfiguration to IED(vendor )NUR relay 2 UR relay X