5-36 F60 Feeder Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5i) TFTP PROTOCOLPATH: SETTINGS PRODUCT SETUP COMMUNICATIONS TFTP PROTOCOLThe Trivial File Transfer Protocol (TFTP) can be used to transfer files from the F60 over a network. The F60 operates as aTFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt fileobtained from the F60 contains a list and description of all available files (event records, oscillography, etc.).Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation ofthose protocols.j) IEC 60870-5-104 PROTOCOLPATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-104 PROTOCOLThe F60 supports the IEC 60870-5-104 protocol. The F60 can be used as an IEC 60870-5-104 slave device connected to amaximum of two masters (usually either an RTU or a SCADA master station). Since the F60 maintains two sets of IEC60870-5-104 data change buffers, no more than two masters should actively communicate with the F60 at one time.Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation ofthose protocols. TFTP PROTOCOLTFTP MAIN UDP PORTNUMBER: 69Range: 1 to 65535 in steps of 1MESSAGE TFTP DATA UDP PORT 1NUMBER: 0Range: 0 to 65535 in steps of 1MESSAGE TFTP DATA UDP PORT 2NUMBER: 0Range: 0 to 65535 in steps of 1 IEC 60870-5-104 PROTOCOLIEC 60870-5-104FUNCTION: DisabledRange: Enabled, DisabledMESSAGE IEC TCP PORTNUMBER: 2404Range: 1 to 65535 in steps of 1MESSAGE IEC NETWORK CLIENT ADDRESSESMESSAGE IEC COMMON ADDRESSOF ASDU: 0Range: 0 to 65535 in steps of 1MESSAGE IEC CYCLIC DATAPERIOD: 60 sRange: 1 to 65535 s in steps of 1MESSAGE IEC CURRENT DEFAULTTHRESHOLD: 30000Range: 0 to 65535 in steps of 1MESSAGE IEC VOLTAGE DEFAULTTHRESHOLD: 30000Range: 0 to 65535 in steps of 1MESSAGE IEC POWER DEFAULTTHRESHOLD: 30000Range: 0 to 65535 in steps of 1MESSAGE IEC ENERGY DEFAULTTHRESHOLD: 30000Range: 0 to 65535 in steps of 1MESSAGE IEC OTHER DEFAULTTHRESHOLD: 30000Range: 0 to 65535 in steps of 1MESSAGE IEC REDUNDANCYENABLED: NoRange: No, YesNOTENOTE