5-140 F60 Feeder Protection System GE Multilin5.6 GROUPED ELEMENTS 5 SETTINGS5d) PHASE INSTANTANEOUS OVERCURRENT (ANSI 50P)PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) PHASE CURRENT PHASE IOC 1(8)The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as adefinite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timingcurves are shown below for form-A contacts in a 60 Hz system. PHASE IOC1PHASE IOC1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE PHASE IOC1 SIGNALSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE PHASE IOC1PICKUP: 1.000 puRange: 0.000 to 30.000 pu in steps of 0.001MESSAGE PHASE IOC1 PICKUPDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE IOC1 RESETDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE IOC1 BLOCK A:OffRange: FlexLogic™ operandMESSAGE PHASE IOC1 BLOCK B:OffRange: FlexLogic™ operandMESSAGE PHASE IOC1 BLOCK C:OffRange: FlexLogic™ operandMESSAGE PHASE IOC1TARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE PHASE IOC1EVENTS: DisabledRange: Disabled, Enabled